4-6 ADAM-5000
I/O Modules
Note: If the above procedure is ineffective, the user must
first issue an RTD Self Calibration command $aaSi2
to the module and then complete steps 4 and 5 after
self calibration is complete.
Calibration resistances (ADAM-5013)
Table 4-2: Calibration resistances of ADAM-5013
Input Range
Code (Hex)
Input Range Span
Calibration
Resistance
Zero
Calibration
Resistance
20 Pt, -100 to 100° C
A = 0.00385
140 Ohms 60 Ohms
21 Pt, 0 to 100° C
A = 0.00385
140 Ohms 60 Ohms
22 Pt, 0 to 200° C
A = 0.00385
200 Ohms 60 Ohms
23 Pt, 0 to 600° C
A = 0.00385
440 Ohms 60 Ohms
24 Pt, -100 to 100° C
A = 0.00392
140 Ohms 60 Ohms
25 Pt, 0 to 100° C
A = 0.00392
140 Ohms 60 Ohms
26 Pt, 0 to 200° C
A = 0.00392
200 Ohms 60 Ohms
27 Pt, 0 to 600° C
A = 0.00392
440 Ohms 60 Ohms
28 Ni, -80 to 100° C 200 Ohms 60 Ohms
29 Ni, 0 to 100° C 200 Ohms 60 Ohms