Advantech RS-485 Manual de usuario Pagina 269

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 348
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 268
ADAM-5000 6-147
Chapter 6
$aaSiCjAhEs $aaSiCjAhEs
Name Set Alarm Disable/Latch
Description The addressed counter module is instructed to set alarm
disable or latch.
Syntax $aaSiCjAhEs(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
SiCj identifies the desired slot i and the desired channel j.
AhEs is the command for setting Alarm Disable/Latch
Mode command.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
s indicates alarm enable/disable and can have the value
D = Disable, E=Enable
(cr) represents terminating character, carriage return (0Dh)
Response !aa(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
(cr) represents terminating character, carriage return (0Dh)
Vista de pagina 268
1 2 ... 264 265 266 267 268 269 270 271 272 273 274 ... 347 348

Comentarios a estos manuales

Sin comentarios