6-90 ADAM-5000
Command Set
6.8 Analog Output Command Set
Command Syntax Command Name Description
$aaSiCjArrff Configuration Sets the output range, data
format and slew rate for a
specified channel in a
specified analog output
module in a specified
system.
$aaSiCjB Configuration Status Returns the configuration
parameters of a specified
channel in a specified analog
output module of a specified
system.
#aaSiCj(data) Analog Data Out Sends a digital value from
the host computer to a
specified channel of a
specified slot in a specified
ADAM-5000 system for
output as an analog signal.
$aaSiCj4 Start-Up Output
Current/Voltage
Configuration
Stores a default output value
in a specified channel. The
output value will take effect
upon startup or reset.
$aaSiCj0 4 mA Calibration Directs the specified channel
to store parameters following
a calibration for 4 mA output
$aaSiCj1 20 mA Calibration Directs the specified channel
to store parameters following
a calibration for 20 mA
output
$aaSiCj3hh Trim Calibration Trims the specified channel a
specified number of units up
or down
$aaSiCj6 Last Value Readback Returns either the last value
sent to the specified channel
by a #aaSiCj(data)
command, or start-up output
current/voltage.
5024 Analog Output