5-24 ADAM-5000
Software Utilities
CJC Calibration
1. Prepare an accurate voltage source.
2. Run the zero calibration and span calibration function.
3. Use a temperature emulation device (such as Micro-10) to send a
temperature signal to the ADAM module and then compare this
signal with the value from the ADAM module. If the value is
different from the signal, adjust the CJC value to improve it.
Note: CJC (cold junction sensor) calibration only applies to
the ADAM 4011, 4011D, 4018, 4018M, 5018
Analog Input Resistance Calibration
Modules: ADAM 4013
Analog Output Calibration
ADAM 4021, ADAM 5024: 4 mA and 20 mA
ADAM 4016: 0 V and 10 V