Advantech RS-485 Manual de usuario Pagina 226

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 348
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 225
6-104 ADAM-5000
Command Set
$aaSiCj3hh $aaSiCj3hh
(cr) is the terminating character, carriage return (0Dh)
Example command: $07S1C2314(cr)
response: !07(cr)
The command tells channel 2 of the analog output
module in slot 1 of the ADAM-5000 system at address
07h to increase its output value by 20 (14h) counts
which is approximately 30 µA.
The analog output module confirms the increase.
Note: In order to perform a Trim Calibration, either a mA
meter or a resistor and voltmeter should be connect-
ed to the module's output prior to calibration. (See
also the 4 mA and 20 mA Calibration commands of
the analog output module's command set. Refer also
to Chapter 4, Section 4.5, Analog Output Calibration
for a detailed description.)
5024 Analog Output
Vista de pagina 225
1 2 ... 221 222 223 224 225 226 227 228 229 230 231 ... 347 348

Comentarios a estos manuales

Sin comentarios