6-122 ADAM-5000
Command Set
5080 Counter/
Frequency Module
$aaSiArrff $aaSiArrff
Name Set Configuration
Description Set slot index and counter mode.
Syntax $aaSiArrff(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
configure.
Si identifies the I/O slot i you want to configure.
A is command for setting I/O module configuration.
rr indicates which mode is.
rr=00 represents Bi-direction counter mode.
rr=01 represenrs UP/DOWN counter mode.
rr=02 represents Frequency mode.
ff indicates which format is
ff=00 represents the engineer format.
ff=02 represents the hexdecimal format.
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exists.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh)