Advantech RS-485 Manual de usuario Pagina 162

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 348
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 161
6-40 ADAM-5000
Command Set
$aaSiB $aaSiB
Name Configuration Status
Description Returns the configuration status parameters for a
specified analog input module of a specified system.
Syntax $aaSiB(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si identifies the I/O slot you want to read.
B is configuration status command.
(cr) is the terminating character, carriage return (0Dh)
Response !aarrff(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
rr represents the 2-character hexadecimal code of the
input range.
ff is a hexadecimal number that equals the 8-bit parame-
ter representing data format. Bit 0 and 1 represent data
format. Bit 7 represents integration time. (See Configura-
tion Command $aaSiArrff).
5017/5018 Analog Input