Vista de pagina 144
ADAM-5000 6-23
Chapter 6
$aaSiB $aaSiB
Name RTD Configuration Status
Description Returns the configuration parameters for a specified
RTD input module in a specified system.
Syntax $aaSiB(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si identifies the desired slot i (i:0to3)
B represents the configuration status command
(cr) is the terminating character, carriage return (0Dh).
Response. !aarrff(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
rr represents the 2-character hexadecimal code of the
input range. (See Appendix B)
ff is a hexadecimal number that equals the 8-bit parame-
ter representing data format. Bits 0 and 1 represent data
format. Bit 7 represents integration time (See RTD
Configuration Command $aaSiArrff).