ADAM-5000 6-159
Chapter 6
$aaSiCjRhU $aaSiCjRhU
Name Read Alarm Limit
Description Return the High/Low alarm limit value for the specified
input channel in the addressed ADAM-5000 system
Syntax $aaSiCjRhU(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
SiCj identifies the desired slot i and the desired channel
j.
RhU is the Read Alarm Limit command.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(data)(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
(data) represents the desired alarm limit setting. The
format is always in engineering units. Be aware that
(data) has 10 characters.
(cr) represents terminating character, carriage return
(0Dh)