ADAM-5000 6-155
Chapter 6
$aaSiCjRhC $aaSiCjRhC
Name Read Alarm Connection
Description Return the High/Low alarm limit output connection of a
specified input channel in the addressed ADAM-5000
system
Syntax $aaSiCjRhC(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
SiCj identifies the desired slot i and the desired channel j.
RhC is the command for reading Alarm Connection.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
(cr) represents terminating character, carriage return (0Dh)
Response !aaSkCn(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
SkCn identifies the desired slot k and the desired digital
output point n (n : 0 to F) to which the input alarm is
connected. If the values of k and n are ‘*’, the analog
input has no connection with a digital output point.
(cr) represents terminating character, carriage return (0Dh)