Command Set
5013 RTD Input
$aaSi5mm
Name Enable/Disable Channels for multiplexing
Description Enables/Disables multiplexing for separate channels of
the specified input module
Syntax $aaSi5mm(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system.
Si identifies the I/O slot of the system.
5 represents the enable/disable channels command.
mm are two hexadecimal values. Each value is interpret-
ed by the module as 4 bits. The first 4-bit value is 0. The
second 4-bit value represents the status of channels 0 to
3. A value of 0 means the channel is disabled, while a
value of 1 means the channel is enabled. (See the Read
Channel Status Command $aaSi6).
Note: Bit 4 can not enable a channel in the ADAM-
5013 since the module is physically limited to 3
channels.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
6-30 ADAM-5000