Chapter 5
5.1.12 Alarm Setting
Set the alarm status, high alarm value, low alarm value, and then
click the Update button.
Alarm setting: Disables or enables the alarm either in Latching or
Momentary mode.
High alarm value: Downloads the high alarm limit value into the
module. The format is always in engineering
units.
Low alarm value: Downloads the low alarm limit value into the
module. The format is always in engineering units.
Digital Filter
High level voltage: Set the high trigger level for non-isolated input
signals. The range is from 0.1 V to 5.0 V. This
high trigger level must be higher than the low
trigger level at all times.
ADAM-5000 5-19