Advantech 5000 Series Manual de usuario Pagina 129

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 301
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 128
Command Set 5017H/5017UH
Analog Input
$aaSiAFFff
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh).
Example command: $35S3AFF00(cr)
response: !35(cr)
The data format of the ADAM-5017H / 5017UH module in
slot 3 of the ADAM-5000 system at address 35h is
configured for engineering unit format. The response
indicates that the command has been received as a valid
command.
6-64 ADAM-5000
Vista de pagina 128
1 2 ... 124 125 126 127 128 129 130 131 132 133 134 ... 300 301

Comentarios a estos manuales

Sin comentarios