Technical specifications
A-22 ADAM 4000 Series User's Manual
Input Range
Code (Hex)
Input Range Typical
Accuracy
Maximum
Error
Units
0E J thermocouple 0 to
760 C
1.0 1.5 C
0F K thermocouple 0 to
1000 C
1.0 1.5 C
10 T thermocouple -100 to
400 C
1.0 1.5 C
11 E thermocouple 0 to
1000 C
1.0 1.5 C
12 R thermocouple 500 to
1750 C
1.2 2.5 C
13 S thermocouple 500 to
1750 C
1.2 2.5 C
14 B thermocouple 500 to
1800 C
2.0 3.0 C
A.10 ADAM-4021 Analog Output Module
Table A-13 ADAM-4018M Range Accuracy for Thermocouple
NOTE: Because the CJC sensor of ADAM-4018/4018M is located in the
side of channel 0 to 4, the measurement will have the difference ± 1
o
C
between channel 0 ~ 4 and channel 5 ~ 7.