Chapter 4 Command Set 4-117
Chapter 4
@AACE
Name Clear Event Counter
Description The addressed module is instructed to reset its event counter to
zero.
Syntax @AACE(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
CE
Clear Event Counter command.
(cr)
represents terminating character, carriage return (0Dh).
Response !AA(cr)
if the command was valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
!
delimiter character indicating a valid command was received.
AA
represents the 2-character hexadecimal address of the
responding analog input module.
(cr)
represents terminating character,
carriage return (0Dh).
Example command: @09CE(cr)
response: !09(cr)
The command instructs the module at address 09h to set its
event counter to zero.
The module responds that its counter has been reset.
4011, 4011D, 4012, 4014D