4.6.7 CounterPulseStart
Configures the specified counter for pulse output and starts the counter.
Input:
Data type Parameter Description
DevHandle The handler id of the device specified by DevNum as
assigned by the LabVIEW program.
Counter Counter number of the specified device
Period The period time of a pulse (Its unit is a second)
UpCycle The first 1/2 cycle length in seconds for AMD
Am9513A
GateMode Gating mode to be used for AMD Am9513A
error in A cluster containing error information, such as the
status, code, and source elements that is passed from
a previous linked VI.
Output:
Data type
Parameter Description
DevHandle The handler id of the device specified by DevNum as
assigned by the LabVIEW program.
error out A cluster containing error information. If error in
indicated an error, the status, code, and source
elements of error out have the same values as the
corresponding elements of error in