Advantech PCI-1724U Manual de usuario Pagina 58

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 62
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 57
PCI-1724U User Manual 50
Step 2: Select the output range of the channel to 0~20mA or 4~20mA.
Step 3: Click the Calibration button to start the calibration process. The
Calibration Wizard window will pop up.
Figure D.9: Click the Calibration Button to Launch the Calibration
Step 4: Follow the instruction of Calibration Wizard and click the Next
button to proceed to the next step.
Fig.3 The start-up window of offset calibration
Step 5: At this step, the Wizard will output 4 mA on the channel you
selected. Please check the value on the meter is in the range (I). If the
value does not fit, please perform the adjustment.
There are 3 ways to perform the adjustment.
1. Move the slider (II).
2. Input the adjust value (III). Note that only if the [Set] button is pressed,
the value will take effect.
Note Each calibration process can calibrate only one chan-
nel and one input range at a time.
Vista de pagina 57
1 2 ... 53 54 55 56 57 58 59 60 61 62

Comentarios a estos manuales

Sin comentarios