Advantech PCI-1724U Manual de usuario Pagina 53

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 62
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 52
45 Appendix D
D.1 Voltage Calibration Procedure
1. Click the Setup button on the Advantech Device Manager window
(Fig.1) to launch the PCI-1724U Device Setting window (Fig.2).
Figure D.1: Click the Setup button to Launch the Device Setting
2. Select the output range of the channel to –10V~10V.
3. Click the Calibration button to start the calibration process. The
Calibration Wizard window will pop up.
Note Each calibration process can calibrate only one chan-
nel and one input range at a time.
Vista de pagina 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 61 62

Comentarios a estos manuales

Sin comentarios