51 Appendix D
3. Press [Default] button (IV). This action will load the factory default
value.
The value on the meter will change after you change the Adjust Value.
Please check the value on the meter is in the range again. If value fits the
condition, press the [Next] button to continue.
Figure D.10: The Adjustment Process of Offset Calibration
Step 6: After offset calibration, this step is to adjust Span. The Wizard
will output 20mA on the channel you selected. The steps of span calibra-
tion are quite similar to those of the offset calibration (Step 5). Follow the
instructions of the Calibration Wizard. If the value fits the condition,
press the [Next] button to continue.