A.4 Current Sink Calibration
1. Select the 0 ~ +5 V (unipolar) output range for the channel to be
calibrated.
2. Set all digital input codes to 0. Then adjust VRn (n = 5, 6, 7, 8
depending on what channel is to be calibrated, see prior page) until
your ammeters reading is 0.00 mA or 4.00 mA (Depending on
jumper setting JP1 to JP4, see Section 3.1.1).
3. Set all digital input codes to 1. Now, adjust VRn (n = 1, 2, 3, 4
depending on what channel is to be calibrated, see prior page) until
your ammeter shows a reading equal to 20.00 mA.
4. Repeat steps 2 and 3 until both of them are satisfied.