39 PCI-1706U User Manual
Appendix C Calibration
C.1.1 A/D Calibration Wizard
Introduction:
Item 1: Before start calibration, read the instructions:
1. Stop any running operations of the device;
2. Connect your voltmeter to TP1 and AGND, adjust VR1 until the voltage is 2.5 V.
(See this page for the position of TP1/VR1.)
3. Select channels in the following list. Hold CTRL key and left chick the list item
while selecting multiple channels. All channels are selected for default.
Item 2: Display the calibration status and result during the process.