45
C.19 Synchronized strobe — BASE+20H
Write any values to BASE+20H to synchronize all D/A channels.
Table C-18 Register for synchronized strobe
Base Addr.
151413121110987654321 0
Synchronized strobe
20H W
XXXXXXXXXXXXXXXX
Note:
✎ Be sure to enable the synchronize function by write the value to
BASE+12H first. Next, write the specific data into BASE+00H ~ 0FH.
Last, to write any value to this register to synchronize all D/A channels.
✎ On the other hand, it you didn’t enable the synchronize function by write
the value to BASE+12H first, all the specific data which write to
BASE+00H ~ 0FH will be output immediately!
C.20 Reset all D/A channels strobe — BASE+22H
Write any values to BASE+22H to reset all D/A channels.
Table C-19 Register for reset all D/A channels strobe
Base Addr.
151413121110987654321 0
Reset all D/A channels strobe
22H W
XXXXXXXXXXXXXXXX