Chapter 2 2-5 2.2 ADAM-5017 8-channel analog input module The ADAM-5017 is a 16-bit, 8-channel analog differential input module that provides pro
Analog Input module 2-6 ADAM 5000 IO modules User’s Manual Application wiring Figure2-4: Millivolt and volt input Figure 2-5: Process cur
Chapter 2 2-7 Technical specifications of ADAM-5017 Analog Input Channels Eight differential Input Type mV, V, mA Input Range ± 150 mV, ± 5
Analog Input module 2-8 ADAM 5000 IO modules User’s Manual 2.3 ADAM-5017H 8-channel high speed analog input module The ADAM-5017H is a 12-bit plus
Chapter 2 2-9 Application wiring Figure 2-7: Millivolt and volt input Figure 2-8: Process current input
Analog Input module 2-10 ADAM 5000 IO modules User’s Manual Figure 2-9: Locations of 125-ohm resistors Note: To maintain measurement accu
Chapter 2 2-11 Technical specifications of ADAM-5017H Analog Input Channels 8 differential ADC Resolution 12 bits, plus sign bit Type of ADC
Analog Input module 2-12 ADAM 5000 IO modules User’s Manual Input Range With Overranging Offset Error @ 25°C Offset Error @ -10 to +70°C Gain
Chapter 2 2-13 2.4 ADAM-5018 7-channel thermocouple input module The ADAM-5018 is a 16-bit, 7-channel thermocouple input module that features pro
Analog Input module 2-14 ADAM 5000 IO modules User’s Manual Application wiring Figure 2-11: Thermocouple input
I/O Module Introduction ADAM-5000 Series I/O Module User’s Manual Table of Contents Chapter 1 Introduction ….……...…...
Chapter 2 2-15 Technical specifications of ADAM-5018 Analog Input Channels Seven differential Input Type mV, V, mA, Thermocouple Input Ran
Analog Output Module 3
Analog Output Module 3-2 ADAM 5000 IO modules User’s Manual 3.1 ADAM-5024 4-channel analog output module The ADAM-5024 is a 4-channel analog outp
Chapter 3 3-3 Application wiring Figure 3-2: Analog output Technical specifications of ADAM-5024 Analog Output Channels Four Output Type
Digital Input/Output Modules 4
Digital Input/Digital Output Module 4-2 ADAM 5000 IO modules User’s Manual 4.1 ADAM-5050 16-channel universal digital I/O module The ADAM-5050 feat
Chapter 4 4-3 Application wiring Figure 4-3: Dry contact signal input (ADAM-5050) Figure 4-4: Wet contact signal input (ADAM-5050) Figur
Digital Input/Digital Output Module 4-4 ADAM 5000 IO modules User’s Manual Technical specifications of ADAM-5050 Points 16 Channel Setting Bitwise
Chapter 4 4-5 4.2 ADAM-5051 series digital input module 4.2.1 ADAM-5051(D) 16-channel digital input module The ADAM-5051 provides sixteen digital
Digital Input/Digital Output Module 4-6 ADAM 5000 IO modules User’s Manual Figure 4-8: Contact closure input (ADAM-5051/5051D) Technical spe
I/O Module Introduction ADAM-5000 Series I/O Module User’s Manual Chapter 5 Serial Communication Module………..…... 5-1 5.1 ADAM-5
Chapter 4 4-7 4.2.2 ADAM-5051S 16-channel Isolated Digital Input Module with LED The ADAM-5051S provides 16 isolated digital input channels for c
Digital Input/Digital Output Module 4-8 ADAM 5000 IO modules User’s Manual Technical specification of ADAM-5051S Point 16(4-channel/group) Digi
Chapter 4 4-9 4.3 ADAM-5052 8-channel isolated digital input module The ADAM-5052 provides eight fully independent isolated channels. All have 50
Digital Input/Digital Output Module 4-10 ADAM 5000 IO modules User’s Manual Technical specifications of ADAM-5052 Points 8 Differential Digital
Chapter 4 4-11 4.4 ADAM-5055S 16-channel Isolated Digital I/O Module with LED The ADAM-5056S provides 8 isolated digital input and 8 isolated outp
Digital Input/Digital Output Module 4-12 ADAM 5000 IO modules User’s Manual Technical specification of ADAM-5055S Points 16 Digital Output 8 (
Chapter 4 4-13 4.5 ADAM-5056(D) series digital output module w/LED 4.5.1 ADAM-5056(D) 16-channel digital output module w/LED The ADAM-5056 featur
Digital Input/Digital Output Module 4-14 ADAM 5000 IO modules User’s Manual Technical specifications of ADAM-5056 There are 16-point digital input
Chapter 4 4-15 Application wiring Figure 4-18: ADAM-5056S module wiring diagram Points 16(8-channel/group) Digital Output Open collector
Digital Input/Digital Output Module 4-16 ADAM 5000 IO modules User’s Manual 4.5.3 ADAM-5056SO 16-channel Isolated Digital Output Module with LED Th
Introduction 1
Chapter 4 4-17 Technical Specification of ADAM-5056SO Points 16(8-channel/group) Digital Output Open collector to 40 V 200 mA max load per cha
Digital Input/Digital Output Module 4-18 ADAM 5000 IO modules User’s Manual 4.6 Relay Output Modules 4.6.1 ADAM-5060 relay output module The ADA
Chapter 4 4-19 Technical specifications of ADAM-5060 Points 6, two Form A and four Form C Contact rating AC: 125 V @ 0.6A; 250 V @ 0.3 A DC:
Digital Input/Digital Output Module 4-20 ADAM 5000 IO modules User’s Manual Application wiring Figure 4-24: Relay output Technical specifi
Chapter 4 4-21 4.6.3 ADAM-5069 power relay output module The ADAM-5069 power relay output module provides 8 relay channels of Form A. Switches ca
Digital Input/Digital Output Module 4-22 ADAM 5000 IO modules User’s Manual 4.7 Counter/Frequency Module Overview Compatible ADAM-5000 Series Ma
Chapter 4 4-23 Alarm Setting Function While in counter mode, you can set alarm status--Disable and Latch. If you want to disable it, you can selec
Digital Input/Digital Output Module 4-24 ADAM 5000 IO modules User’s Manual ADAM-5080 Application Wiring Figure 4-27: Isolated Input Level Fi
Chapter 4 4-25 ADAM-5080 Counter/Frequency Mode Selection Users can select Bi-direction, Up/Down Counter or Frequency option as shown in Figure 44
Digital Input/Digital Output Module 4-26 ADAM 5000 IO modules User’s Manual Figure 4-30: Wiring for Up/Down Counting Note: If you need only
Introduction 1-2 ADAM 5000 IO modules User’s Manual This manual introduces the detail specifications functions and application wiring of each ADAM-
Chapter 4 4-27 Features -- Frequency Mode If users want to select frequency mode, they can only utilize Up Counting type, and can only connect to
Digital Input/Digital Output Module 4-28 ADAM 5000 IO modules User’s Manual Setting Initial Counter Value In order to utilize the alarm function, u
Chapter 4 4-29 Getting the Totalizer Value If users want to get the actual counter value, a formula such as follows can facilitate an easy calcul
Digital Input/Digital Output Module 4-30 ADAM 5000 IO modules User’s Manual Features--Digital Output Mapping If users want to use Digital Output f
Chapter 4 4-31 TTL/Isolated Input Level According to your need, you can select either TTL or Isolated Input Level by setting the configuration for
Digital Input/Digital Output Module 4-32 ADAM 5000 IO modules User’s Manual ADAM-5080 Technical Specifications Channel 4 Input Frequency 0.3 ~
Serial Communication Module 5
Serial Communication Module 5-2 ADAM 5000 IO modules User’s Manual Overview Compatible ADAM-5000 Series Main Units The ADAM-5090 is a 4-port RS-2
Chapter 5 5-3 Communication Backup Function With the ADAM-5090 you can implement dual communication channels between your PC and the ADAM system.
Serial Communication Module 5-4 ADAM 5000 IO modules User’s Manual PIN Mapping PIN Name RJ-48 DB9 /DCD 1 1 RX 2 2 TX 3 3 /DTR
Analog Input Modules 2
Chapter 5 5-5 I/O Slots and I/O Ports Numbering The ADAM-5090 module provides four RS-232 ports for communication with target devices. The ports a
Serial Communication Module 5-6 ADAM 5000 IO modules User’s Manual LED Status of the ADAM-5090 Module There are two LEDs for each port on the fron
Chapter 5 5-7 port_set_speed(1,115200L); //Enable Port FIFO. Here we enable 128 byte FIFO for port1. port_enable_fifo(1); //After these abov
Analog I/O Modules Calibration 6
Analog I/O Modules Calibration 6-2 ADAM 5000 IO modules User’s Manual Analog input/output modules are calibrated when you receive them. However, ca
Chapter 6 6-3 Figure 6-2: Zero calibration 5. Execute the Span Calibration command. This can be done with the ADAM utility software. Figure
Analog I/O Modules Calibration 6-4 ADAM 5000 IO modules User’s Manual 6. CJC Calibration (only for T/C input module) Figure 6-4: Cold junction
Chapter 6 6-5 Calibration voltage (ADAM-5017/5018) Module Input Range Code (Hex) Input Range Span Calibration Voltage 00h ±15 mV +15 mV
Analog I/O Modules Calibration 6-6 ADAM 5000 IO modules User’s Manual Calibration voltage (ADAM-5017H) Module Input Range Code (Hex) Input Range
Chapter 6 6-7 6.2 ADAM-5013 RTD Input Resistance Calibration 1. Apply power to the module and let it warm up for about 30 minutes. 2. Make su
Analog Input module 2-2 ADAM 5000 IO modules User’s Manual Analog input modules use an A/D converter to convert sensor voltage, current, thermocoup
Analog I/O Modules Calibration 6-8 ADAM 5000 IO modules User’s Manual Calibration resistances (ADAM-5013) Input Range Code (Hex) Input Range Sp
Chapter 6 6-9 6.3 Analog output module calibration The output current of analog output modules can be calibrated by using a low calibration value
Analog I/O Modules Calibration 6-10 ADAM 5000 IO modules User’s Manual 4. Issue the Analog Data Out command to the module with an output value of
Chapter 2 2-3 Application wiring Figure 2-2: RTD inputs
Analog Input module 2-4 ADAM 5000 IO modules User’s Manual Technical specifications of ADAM-5013 Analog input channels three Input type Pt or
Comentarios a estos manuales