www.advantech.com/products
Online Download
8
5
44
10
ICOM
9
Motion Control
8
ADAM-3000
7
cPCI
6
DA&C
ATM & AWS
FPM
3
TPC
2
IPPC
1
Software
11
eConnectivity
12
UNO
13
ADAM-4000
14
ADAM-5000
15
ADAM-6000
16
ADAM-8000
17
BAS
13-19
All product specifications are subject to change without notice Last updated : January 2005
Specifications
Analog Input
Effective Resolution 16-bit
Channels Six differential, two
single-ended (4017)
eight differential (4017+)
Channel Independent ADAM-4017+ only
Configuration
Modbus
®
ADAM-4017+ only
lnput Type mV, V, mA
lnput Range ±150 mV, ±500 mV, ±1
V, ±5 V, ±10 V, ±20 mA,
4~20mA (4017+ only)
Isolation Voltage 3000 V
DC
Fault and Overvoltage Withstands overvoltage
Protection
up to ±35 V
Sampling Rate 10 samples/sec. (total)
Input Impedance 20 MΩ
Bandwidth 13.1 Hz @ 50 Hz,
15.72 Hz @ 60 Hz
Accuracy ±0.1% or better
Zero Drift ±6 µV/° C
Span Drift ±25 ppm/° C
CMR @ 50/60 Hz 92 dB min.
Built-in Watchdog Timer
Power Requirements Unregulated +10 ~
+30 V
DC
Power Consumption 1.2 W @ 24 V
DC
Built-in TVS/ESD Protection
Ordering Information
ADAM-4017-D2 8-channel Analog Input
Module
ADAM-4017+ 8-channel Differential Analog
Input Module w/Modbus
®
8-channel Analog Input Module
with Modbus
®
8-channel Thermocouple Input
Module with Modbus
®
8-channel Analog Input Data
Logger
Specifications
Analog Input
Effective Resolution 16-bit
Channels Six differential, two
single-ended (4018)
eight differential (4018+)
Ch. Independent Conf. ADAM-4018+ only
Modbus
®
ADAM-4018+ only
lnput Type Thermocouple, mV,
V, mA (4018) (4018+
Supports T/C & 4~20
mA only)
lnput Range ±15 mV, ±50 mV, ±100
mV, ±500 mV, ±1 V, ±2.5
V, ±20 mA (4018);
4~20 mA (4018+)
T/C Type and Temperature Ranges
J
0 ~ 760° C
R
500 ~1750° C
K
0 ~ 1370° C
S
500 ~1750° C
T
-100 ~ 400° C
B
500 ~1800° C
E
0 ~ 1000° C
Isolation Voltage 3000 V
DC
Fault and Overvoltage Resists overvoltage up
Protection
to ±35 V
Sampling Rate 10 samples/sec. (total)
Input Impedance 20 MΩ
Bandwidth 13.1 Hz @ 50 Hz,
15.72 Hz @ 60 Hz
Accuracy ±0.1% for voltage input
Zero Drift ±3 µV/°
C
Span Drift ±25 ppm/° C
CMR @ 50/60 Hz 92 dB min.
Built-in Watchdog Timer and Individual wire
burned-out detection (4018+ only)
Power Requirements Unregulated +10 ~
+30 V
DC
Power Consumption 0.8 W @ 24 V
DC
Built-in TVS/ESD Protection
Ordering Information
ADAM-4018-D2 8-ch. Th.couple Input Module
ADAM-4018+ 8-ch. Differential, mA and
Thermocouple Input Module
w/Modbus
®
Specifications
Analog Input
Effective Resolution 16-bit
Channels Six differential, two
single-ended
lnput Type Thermocouple, mV, V,
mA
lnput Range ±15 mV, ±50 mV, ±100
mV, ±500 mV, ±1 V, ±2.5
V, ±20 mA
T/C Type and Temperature Range
J
0 ~ 760° C
R
500 ~1750° C
K
0 ~ 1370° C
S
500 ~1750° C
T
-100 ~ 400° C
B
500 ~1800° C
E
0 ~ 1000° C
Isolation Voltage 3000 V
DC
Sampling Rate 10 samples/sec. (total)
Input Impedance 1.8 MΩ
Bandwidth 13.1 Hz @ 50 Hz,
15.72 Hz @ 60 Hz
Accuracy ±0.1% for voltage input
Zero Drift ±3 µV/° C
Span Drift ±25 ppm/° C
CMR @ 50/60 Hz 92 dB min.
Storage
Capacity 38,000 samples (total)
(128 KB flash memory)
Storage Mode Write to end of memory
& cyclic
Logging Mode Internal log or event log
(high/low)
Sampling Interval 2 secs. ~ 18 hours
Built-in Watchdog Timer
Power Requirements Unregulated +10 ~
+30 V
DC
Power Consumption 1.8 W @ 24 V
DC
Ordering Information
ADAM-4018M 8-channel Analog Input
Data logger – mV, V, mA, or
thermocouple
ADAM-4017+
ADAM-4018+
ADAM-4018M
ADAM-4017/4017+ ADAM-4018/4018+ ADAM-4018M
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com