75 EKI-1528/1526 User Manual
Chapter 6 Telnet/Serial Console Configuration
[Usage] port nn||all type 232|422|485 flow 0|1|2|3
[Function] Set serial ports’ type and flow control
Flow 0: None
Flow 1: XOn/XOff
Flow2: RTS/CTS
Flow3: DTR/DSR
[Usage] port nn|all baud XXXX parity n|e|o|m|s data 5|6|7|8 stop 1|1.5|2
[Function] Set the serial ports’ baud rate, parity, data bits, and stop bits.
Acceptable baud rate: 50, 75, 110, 150, 300, 600, 1200, 1800, 2400, 4800, 7200,
9600, 14400, 19200, 38400, 57600, 115200, 230400, 460800, and 921600
Parity n: None
Parity e: Even
Parity o: Odd
Parity m: Mark
Parity s: Space
[Usage] port nn|all mode vcom|ctrl|data
[Function] Set the serial ports as virtual COM mode, control mode, or data mode
mvcom
Show and setup the VCOM mode